DX SERIES
TEMPERATURE CONTROLLER
TEMPERATURECONTROLLER
3


Theactionforeachalarmbecomesasfollows:
(▲:Set-value(SV)▵:Alarmset-value)
If a measured value exceeds the high setting range
limitduetoupscale,etc.,measured-valuedisplaystarts
flashing.
Further,ifitexceedsthehighinputdisplayrangelimit,
themeasured-value(PV)displayunitflashesoverscale
display
“”
Ifameasured-valuebecomesbelowthelowsetting
rangelimitduetodownscale,etc.,measured-value
displaystartsflashing.
Further,ifitbecomesbelowthelowinputdisplay
rangelimit,themeasured-value(PV)displayunit
flashesunder-scaledisplay
“”
·After power is applied, the low alarm is turned on
during the temperature rises. If this is not desired, the
low alarm can be suspended after power is applied until
the temperatre goes out of the alarm setting range by
addingtheholdfunction.(Fig.2)
As shown in the following diagram, each of the power,
input, MCU, and output blocks of the DX9 is mutually
isolated.

(1)SettheDipswitchontheinnerPCBtoINITIALset.

(2)Turnonthepower,then displaysontheProcess
Valuedisplayunit(PV),whichisinthestateofinitial
setting.
(3)Pushthemodekey,thentheParameterswillbe
changedasfollows:


✽ BandalarmoperatesonlyALHrelay.
ON
ALH
High
OFF
ALL
ON
Low
ON
ALH
High
OFF
ALL
Low
OFF
ON
ALH
High
OFF
ALL
ON
Low
ON
ALH
High
OFF
ALL
Low
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
Withoutholdfunction
setpoint
(Lowalarm)
PVvalue PVvalue
PowerON
fig.1
fig.2
Alarmoutput Alarmoutput
PowerON
setpoint
(Lowalarm)
Withholdfunction
DX9circuitconfiguration
Power
supply
Isolated
Isolated
Isolated
Isolated
Isolated
Input
MCU Output
·Freelyadjustablehysteresis
Adjustablerange:0-100or0.0-100.0℃(℉,or%)
Low High
OFF
ON
Low High
OFF
ON
Controloutput
Hysteresiswidth
Hysteresiswidth
Highalarm
setpoint setpoint

0000
0001
0010
0011
0100
0101

CurrentorVoltage
K(CA)
JISPt100Ω
DINPt100Ω
R(PR)
J(IC)
PV-displayUnit
SV-displayUnit
(Inputmodefixed)
[] [] [] []
<CAUTION>
Do the setting according to the specifications of the
controllersupplied.Ifyouselectwronginputoroutput,it
causes the malfunctions. Set according to the input or
outputspecificationsasshowninsideoffrontlid.

High&Lowalarm
Bandalarm

High&Lowalarm
Bandalarm